| Series | LH10-23BxxR2 |
| Model | LH10-23B24R2 |
| Brand | MORNSUN |
| Input Voltage Range (AC) | 85–305 VAC |
| Input Voltage Range (DC) | 100–430 VDC |
| Input Frequency | 47–63 Hz; 115VAC: 0.26 Hz |
| Input Current | 230VAC: 0.16A max; 115VAC: 13A |
| Inrush Current | 23A @230VAC |
| Leakage Current | 0.25mA typ, RMS Max. max @270VAC/50Hz |
| Recommended External Input Fuse | 2A/300V, slow-blow, required |
| Hot Plug | Unavailable |
| Output Voltage Accuracy | 3.3V output: ±3%; Others: ±2% |
| Line Regulation | ±0.5% (Full load) |
| Load Regulation | ±1% (0% -100% load) |
| Ripple & Noise | 50mV typ, 100mV max ((peak-to-peak value)) (20MHz bandwidth) |
| Temperature Coefficient | ±0.02%/°C |
| Stand-by Power Consumption | 0.3W @230VAC |
| Short Circuit Protection | Hiccup, continuous, self-recover |
| Over-current Protection | ≥150% Io, self-recover; 3.3/5V output: ≤7.5VDC typ, (Hiccup) max; 9V output: ≤15VDC typ, (Hiccup) max |
| Over-voltage Protection | 12/15V output: ≤20VDC typ, (Hiccup) max; 24V output: ≤30VDC typ, (Hiccup) max |
| Minimum Load | 0%; 115VAC input: 8% |
| Hold-up Time | ms; 230VAC input: 65 ms |
| Isolation (Input–Output) | 4200 VAC |
| Isolation | VAC (Electric Strength Test for 1min.,) |
| Isolation (Input–⏚) | 2500 VAC (PE) |
| Isolation (Output–⏚) | 1250 VAC (PE) |
| Impulse Withstand Voltage | Input - PE pulses, interval ≥5s. There is no breakdown: 6000 VDC; discharge during the test.: VDC; Output - PE: 6000 VDC; Input - output: 100 VDC |
| Insulation Resistance | Input - PE At 500VDC: 100 MΩ; Output - PE: 100 MΩ |
| Operating Temperature | -40 to +85℃ |
| Storage Temperature | -40–+105℃ |
| Storage Humidity | 95 %RH; Wave-soldering, Max. 10 seconds: 255–265 %RH |
| Soldering Temperature | ℃; Manual-welding, Max. 5 seconds: 350 to 370℃ |
| Switching Frequency | 65kHz; -40℃ to -25℃: 2.67; +55℃ to +70℃: 2.67 %/℃; +70℃ to +85℃: 1.33 |
| Power Derating | 85VAC - 100VAC: 1.67 %/VAC; 277VAC - 305VAC: 0.71; 2000m - 5000m: 6.67 %/Km; EN/BS EN62368-1safety approved;; Design refer to IEC/UL62368-1, IEC62477-1 (9V output) |
| Safety Standard | IEC/EN/BS EN62368-1safety approved; Design refer to UL62368-1; IEC62477-1 |
| Safety Class | CLASS I |
| MTBF | MIL-HDBK-217F@25℃–>500,000 h |
| Case Material | Black plastic, flame-retardant and heat-resistant (UL94V-0) |
| Horizontal package | 55.00 x 45.00 x 21.00 mm |
| Dimension A2 chassis | mounting: 96.10 x 54.00 x 29.50 mm |
| A4 Din-Rail | mounting: 96.10 x 54.00 x 34.10 mm |
| Weight Horizontal | package/A2 chassis package/A4 DIN-rail package: 75g (Typ.)/125g (Typ.)/165g (Typ.) |
| Cooling method | Free air convection |
| EMC Emissions | CE: CISPR32/EN55032 CLASS B; RE: CISPR32/EN55032 CLASS B |
| EMC Immunity | ESD: IEC/EN61000-4-2 Contact ±8KV/Air ±15KV (perf. Criteria A); RS: IEC/EN61000-4-3 10V/m (perf. Criteria A); EFT: IEC/EN61000-4-4 ±4KV (perf. Criteria A); Surge: IEC/EN61000-4-5 line to line ±4KV/line to PE ±6KV; CS: IEC/EN61000-4-6 10Vr.m.s (perf. Criteria A); Voltage dip, short: interruption |