| Series | PJU |
| Model | PJU-13V60WCBA |
| Brand | DELTA |
| V+ (B+) | V+ B+ Battery Input / Output Characteristics |
| Nominal Battery Voltage (12 Vdc) | 24 Vdc 2 x 12 Vdc SLA Sealed lead acid battery |
| Battery Voltage Range | Continuously 10.5 to 12.5 Vdc (nominal at 12 V) 22.0 to 26.7 Vdc (nominal at 24 V) Operating Maximum |
| 16 Vdc Max | 32 Vdc Max Allowed Voltage Battery Low |
| Voltage1) (11.5 Vdc typ.) | 22.5 Vdc typ. Minimum |
| 10.0 Vdc ± 0.5 Vdc | 18.0 Vdc ± 0.5 Vdc Voltage2) |
| Battery Capacity (3.2 AH – 15 AH) | 3.2 AH – 7 AH Charging Time3) > 12 hrs for battery 7 AH > 12 hrs for battery 7 AH |
| Buffering Time4) (Approx. 1 hr) | Approx. 3 hrs 20 mins |
| for battery 12 V/7 AH | for battery 24 V/7 AH |
| Recommended External Fuse for Battery | Automotive 20 A / 80 V, FK3 type from Littelfuse, or similar in the battery B+ path. The battery fuse protects the wires between the battery and the unit. |
| Battery Charging (Normal Mode) | CC-CV mode (constant current-constant voltage) |
| End-of-Charge Voltage | The unit always charges battery to a fixed voltage value 1) The voltage level of battery to enable “BAT Low” indication function, for PJU-☐V60W☐B☐ model only B+ and B- terminals; and, with input and output loads disconnected. discharged at. For larger capacity, charging time will be more. charge/discharge cycles & battery discharge plot from battery manufacturer. PJU Open Frame Power Supply with Integrated DC-UPS |
| Case Chassis / Cover | SECC |
| Dimensions (L x W x H) (Enclosed) | 103.4 x 62 x 37 mm (4.07 x 2.44 x 1.46 inch) |
| L Frame | 103.4 x 61.45 x 37 mm (4.07 x 2.42 x 1.46 inch) |
| Unit Weight (Enclosed) | 0.25 kg (0.56 lb) |
| LED Indicator (Green LED) | DC OK |
| Cooling System | Convection |
| Terminal (PJU-☐V60W☐☐A) | Input 3 Pins (Rated 300 V/16 A) |
| Output with Signal | PJU-☐V60W☐BA 6 Pins (Rated 300 V/8 A) Mating Connector: VHR-5N Terminal: SVH-21T-P1.1 |
| Wire (PJU-☐V60W☐☐A) | Input AWG 22-12 AWG 24-12 |
| Output (AWG 22-16) | AWG 24-16 |
| Output with Signal (AWG 22-16) | AWG 24-16 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA PJU Open Frame Power Supply with Integrated DC-UPS PJU-60 W Series / PJU-□V60W□□□ Buffering Times VS Output Load and Battery Capacity PJU-13V60W☐☐☐ 1,000 |
| Current (3.2 AH) | 7 AH 12 AH 15 AH |
| 0.5 A (200) | 460 765 960 |
| 1.3 A (75) | 172 285 355 Buffering Time (min) |
| 2.1 A (45) | 105 170 210 |
| 2.9 A (30) | 74 118 148 |
| 3.5 A (25) | 60 95 120 |
| 4.3 A (19) | 45 75 92 Buffering time above is approx. calculated number and will vary from unit capacity. Buffering time will also vary with different type of battery and |
| 0.5 (1.3) | 2.1 2.9 3.5 4.3 Output Current (A) |
| 3.2AH (7AH) | 12AH 15AH |
| Fig. 1 | Buffering Time VS Output Current (PJU-13V60W☐☐☐) PJU-27V60W☐☐☐ |
| 600 (Current) | 3.2 AH 5 AH 7 AH |
| 0.5 A (275) | 428 615 |
| 0.8 A (165) | 256 375 Buffering Time (min) |
| 400 (1.1 A) | 115 180 265 |
| 1.4 A (85) | 135 200 |
| 1.7 A (68) | 106 160 |
| 200 (2.15 A) | 50 80 124 to unit. The calculations are based on ideal battery and charged to fully battery ageing. |
| 0.5 (0.8) | 1.1 1.4 1.7 2.15 Output Current (A) |
| 3.2AH (5AH) | 7AH |
| Fig. 2 | Buffering Time VS Output Current (PJU-27V60W☐☐☐) PJU Open Frame Power Supply with Integrated DC-UPS PJU-60 W Series / PJU-□V60W□□□ Model Number |
| Surrounding Air Temperature (Operating) | -20°C to +70°C |
| Storage | -40°C to +85°C |
| Power De-rating (Temperature) | Vertical base PJU-☐V60WC☐☐ & PJU-☐V60WL☐☐ & PJU-27V60WB☐☐ |
| mounting | > 40°C de-rate power by 1.67% / °C |
| Vertical side | PJU-13V60WC☐☐ & PJU-13V60WL☐☐ |
| Horizontal base | PJU-13V60WB☐☐ |
| Horizontal side | PJU-☐V60WC☐☐ & PJU-☐V60WL☐☐ |
| Input voltage (Vertical base) | PJU-☐V60WC☐☐ & PJU-☐V60WL☐☐ & PJU-27V60WB☐☐ |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50 G for a duration of 11 ms; 3 times per direction, 9 times in total |
| Operating | IEC 60068-2-27, Half Sine Wave: 10 G for a duration of 11 ms; 1 time in X axis |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5-500 Hz; 2.09 Grms; 20 min per axis for all X, Y, Z directions |
| Over Voltage Category | II PJU Open Frame Power Supply with Integrated DC-UPS PJU-60 W Series / PJU-□V60W□□□ Model Number |
| Overvoltage (V+) | <16 V, Latch Mode <34.8 V, Latch Mode |
| B+ (16 Vdc Max will not cause) | 32 Vdc Max will not cause |