| Серия | CliQ VA |
| Модель | DRV-24V120W1PN |
| Тип | Источники питания на DIN-рейке |
| Бренд | DELTA |
| Fig. 1 | Fig. 2 Efficiency Vs Output Load at 24 V |
| Fig. 3 | Fig. 4 Power Factor Vs Output Load at 24 V CliQ VA DIN Rail Power Supply 24 V 120 W 1 Phase / DRV-24V120W1PN Output Ratings / Characteristics* |
| Nominal Output Voltage | 24 Vdc |
| Factory Set Point Tolerance | 24 Vdc ± 1.0% |
| Output Voltage Adjustment Range | 24-28 Vdc |
| Output Current (Nom.) | 5.0 A / 4.28 A Continuously operating at 24 V / 28 V |
| Nom. (7.5 A / 6.75 A) | Power Boost for 5 seconds at 24 V / 28 V, |
| (Slew rate 0.1 A/µsec) | refer to the details in the Functions section |
| Output Power (Nom.) | 120 W / 120 W Continuously operating |
| Nom. (180 W / 189 W) | Power Boost for 5 seconds, refer to the details in the Functions section |
| Power Boost Duration (Typ.) | 5 seconds |
| Max. (7 seconds) | Duration after which output voltage start to droop, refer to the details in the Function section at Overload & Overcurrent Protections |
| Power Boost Recovery Time (Typ.) | 14 seconds Required wait duration before next Power Boost is taken, refer to the details in the Function section |
| Advanced Power Boost (Typ.) | 10 A @ 50 ms, resistive load Output voltage will drop (Refer to the |
| (Slew rate 0.1A/µsec) (Typ.) | 20 A @ 2 ms, resistive load details in the Function section) |
| Typ. | 20 A @ 5 ms, resistive load |
| Line Regulation (Max.) | 20 mV (@ 85-264Vac input, 100% load) |
| Load Regulation (Max.) | 100 mV (@ 85-264Vac input, 0-100% load) |
| PARD** (Max.) | 50 mVpp 20 Hz to 20 MHz, 50 Ohm, warm up for 10 mins *For power de-rating from 60°C to 70°C, see power de-rating on page 10. **PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor. 100 Vac 120 Vac 230 Vac |
| Rise Time (Max.) | 20 ms 0 µF, 24 V, 5.0 A |
| Max. (50 ms) | 5,000 µF, 24 V, 5.0 A |
| Start-up Time (Max.) | 750 ms At 24 V, 5.0 A |
| Hold-up Time (Typ.) | 140 ms At 24 V, 2.5 A |
| Min. (66 ms) | 66 ms 127 ms At 24 V, 2.5 A |
| Typ. (70 ms) | At 24 V, 5.0 A |
| Min. (34 ms) | 34 ms 65 ms At 24 V, 5.0 A |
| Dynamic Response (Max.) | ± 5% @ 0-100% load Slew rate 0.1 A/µsec |
| (Overshoot & Undershoot O/P Voltage) | (@ 5 Hz, 50 Hz & 1 kHz, 50% Duty Cycle) |
| Start-up with Capacitive Loads (Max.) | 10,000 µF |
| Output Capacitance (Typ.) | 4,300 µF Built-in output capacitors |
| Functional (DC OK Relay) | Rated: 30 V at 1 A, resistive load |
| Contact | The relay contact are normally “ON” (closed) when the output (Vout) is greater than 90% of its rated value. (Refer to the details in the Function section) |
| Years alarm | Rated: 30 V Max. with sink current of 10mA Max. signal CliQ VA DIN Rail Power Supply 24 V 120 W 1 Phase / DRV-24V120W1PN Mechanical |
| Case Cover / Chassis | Aluminium and Plastic / Aluminium |
| Indicator (Green LED) | DC OK |
| Red LED | Overload |
| Cooling System | Convection |
| Terminal (Input) | 3 Pins (Rated 600 V / 35 A) |
| Signal | 2 Pins (Rated 300 V / 10 A) |
| Wire (Input) | AWG 18-8 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA Environment |
| Surrounding Air Temperature (Operating) | -25°C to +70°C |
| Storage | -40°C to +85°C |
| Power De-rating (Vertical) | > 60°C de-rate power by 2.5% / °C Mounting |
| Horizontal | > 50°C de-rate power by 2.5% / °C Mounting |
| Рабочая влажность | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 30 G for a duration of 18 ms; 3 times per direction, 6 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Sine Wave: 10-500 Hz; 3 G peak; displacement of 0.35 mm; 60 min per axis for all X, Y, Z directions |
| Bump Test (Operating) | IEC 60068-2-29, Half Sine Wave: 10 G for a duration of 11 ms, 1,000 times per direction, 6,000 times in total |
| Over Voltage Category (III) | According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) CliQ VA DIN Rail Power Supply 24 V 120 W 1 Phase / DRV-24V120W1PN Protections |
| Overvoltage (28.8 – 35.2 V, SELV Output,) | Refer to the details in the Function |
| Hiccup Mode, Non-Latching | section (Auto-Recovery) |
| Constant current, Hiccup | section Mode (Auto-Recovery) |
| Over Temperature (< 80°C Surrounding Air) | Refer to the details in the Function |
| Temperature @ 100% load, | section Non-Latching (Auto-Recovery) |
| Short Circuit (Hiccup Mode, Non-Latching) | Load impedance ≤ 100 mOhm, refer to (Auto-Recovery when the fault the details in the Function section is removed) |
| Transient Surge Voltage Protection | MOV (Metal Oxide Varistor) |
| Internal Fuse at L pin | T 3.15 A |