| Serie | LMF3000-22Bxx |
| Modell | -- LMF3000-22B24 |
| Marke | MORNSUN |
| Input Voltage Range (Rated) | 200–240 VAC |
| Eingangsspannungsbereich (AC) | 180–277 |
| Eingangsspannungsbereich (DC) | 254–390 VDC |
| Input Voltage Frequency | Hz; AC input: 47–63 Hz; Rated input (Certified voltage): 20 Hz |
| Eingangsstrom | 16A max @230VAC |
| Inrush Current (Cold Start) | 230VAC: 50A |
| Leistungsfaktor | PF≥0.95 @230VAC (full load) |
| Start-up Delay Time | 3 s @230VAC, normal temperature, rated load |
| Input Fuse | Built-in fuse: 25A; Under-voltage protection start (Input voltage drops: A; 140–170 A |
| Input Under-voltage Protection | from high to low): VAC; Under-voltage protection release (Input voltage: VAC; 150–180 VAC; rises from low to high): VAC |
| Hot-Plug | Unavailable |
| Ausgangsspannungsgenauigkeit | ±1% (Full load range) |
| Netzregelung | ±0.5% (Rated load) |
| Lastregelung | ±0.5% (0% - 100% load) |
| Minimum Load | 0; 12V/24V: 150 (20MHz bandwidth) |
| Restwelligkeit und Rauschen | mV; 48V: 200mV max ((peak-to-peak value)) |
| Temperaturkoeffizient | ±0.03%/℃ |
| Überbrückungszeit | 230VAC, rated load: 10 ms; Constant current limit, ms; Pin1 and Pin2 of the CON3 are short-circuit connected: ms |
| Kurzschlussschutz | output voltage turn off after 5s, self-recover; Pin1 and Pin2 of the CON3 are open: Constant current limit self-recover; Constant current limit, self-recover; Pin1 and Pin2 of the CON3 are short-circuit connected: self-recover |
| Überstromschutz | output voltage turn off after 5s, self-recover; Pin1 and Pin2 of the CON3 are open: Constant current limit; 12V: ≤19VDC (Output voltage turn off, self-recover) |
| Überspannungsschutz | 24V: ≤35VDC (Output voltage turn off, self-recover); 48V: ≤64VDC (Output voltage turn off, self-recover); 230VAC, Over-temperature protection start: 90 self-recover) |
| Übertemperaturschutz | ℃; 100% load Over-temperature protection release: 50℃ |
| Isolation (Input–⏚) | 2000 VAC |
| Isolation | VAC (Electric strength test for 1min., leakage current) |
| Isolation (Eingang–Ausgang) | 4000 VAC |
| Isolation (Output–⏚) | 1500 VAC |
| Isolationswiderstand | Input - output Relative humidity: < 95%RH, no condensation: 100 MΩ; Output - Test voltage: 500VDC: 100 MΩ |
| Betriebstemperatur | -40 to 85℃ |
| Lagertemperatur | -40–85℃ |
| Betriebsfeuchtigkeit | 10–95 %RH; Non-condensing: %RH |
| Lagerfeuchtigkeit | 20–90%/℃; -40℃ to +50℃: 0 %/℃; Operating temperature derating: %/℃; +50℃ to +85℃: 2.5 %/℃ |
| Power Derating | Input voltage AC Input 180VAC-277VAC: 0 %/VAC; derating DC Input 254VDC-390VDC: 0 %/VAC; Touch current: <0.5mA %/VAC |
| Ableitstrom | 240VAC, 60Hz: EN62368-1,; Earth leakage current: <2mA max EN62368-1,; Design refer to IEC/EN/UL/BS EN62368-1, |
| Sicherheitsstandards | GB4943.1 |
| Schutzklasse | CLASS I |
| MTBF | ≥250,000 h (MIL-HDBK-217F@25℃) |
| Warranty | 5 years (Ambient temperature: ≤85℃) |
| EMV-Emissionen | CE: CISPR32 EN55032 150kHz—30MHz (CLASS B); RE: CISPR32 EN55032 30MHz—1GHz (CLASS A) |
| EMV-Störfestigkeit | Harmonic current: IEC/EN61000-3-2 (CLASS A and CLASS D); ESD: IEC/EN61000-4-2 Contact1±8KV/Air ±15KV; RS: IEC/EN61000-4-3 80MHz – 1GHz 10V/m; EFT: IEC/EN61000-4-4 ±4KV, (5 or 100)kHz; Surge: IEC/EN61000-4-5; CS: IEC/EN61000-4-6 0.15MHz - 80MHz 10Vr.m.s; Voltage dips: IEC/EN61000-4-11 40% U * ,10/12 periods (50/60Hz) (Perf. Criteria B) |