| Serie | CliQ II Buffer Modules |
| Modell | DRB-24V020ABA |
| Typ | Zubehör |
| Marke | DELTA |
| Case Cover / Chassis | Aluminium |
| LED Indicators (Green LED Off) | Unit is discharged or Vin < 22 Vdc |
| Green LED On | Unit is fully charged |
| Green LED Flashing | Unit is charging Slowly (1Hz) |
| Cooling System | Convection |
| Terminal (Input / Output) | 2 Pins (Rated 300 V/30 A) |
| Signal | 5 Pins (Rated 300 V/30 A) |
| Wire (Input / Output) | AWG 12-10 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 40 dBA Environment |
| Surrounding Air Temperature (Operating) | -25°C to +75°C |
| Storage | -25°C to +85°C |
| Power De-rating (Vertical Mounting) | > 70°C de-rate power by 5% / °C |
| Horizontal Mounting | > 70°C de-rate power by 5% / °C |
| Betriebsfeuchtigkeit | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 2,500 Meters (8,200 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 30 G (300 m/S²) for a duration of 18 ms, 1 time per direction, 2 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/S² (3G peak); 60 min per axis for all X, Y, Z direction Protections |
| Overvoltage | 32 V ± 10% |
| Overload / Overcurrent | 30 A Max |
| Kurzschluss | No Damage |
| Penetration Protection | > 3.5 mm (e.g. screws, small parts) |
| Reverse Polarity Protection | Yes |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with PE* connection *PE: Primary Earth CliQ II Buffer Module 24 V 20 A / DRB-24V020AB□ Reliability Data |
| MTBF (at Vin-1V Mode) | > 800,000 hrs. as per Telcordia SR-332 @ Standby Mode (Buffer module in Ready State) |
| Expected Cap Life Time | 10 years (Standby Mode @ 40°C) Safety Standards / Directives |
| Electrical Equipment of Machines | EN/BS EN 60204-1 |
| Electrical Equipment for Use in Electrical Power Installations | IEC/EN/BS EN 62477-1 / IEC 62103 |
| Electrical Safety (SIQ Bauart) | EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CB scheme | IEC 60950-1, IEC 62368-1 |
| UKCA | BS EN 62368-1 |
| Industrial Control Equipment (UL/cUL listed) | UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) |
| CSA | CSA C22.2 No. 107.1-01 (File No. 181564) |
| Hazardous Location / ATEX (cCSAus) | CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 |
| (For DRB-24V020ABA) | [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +75°C (> +70°C derating)] |
| ATEX | II 3G Ex nA IIC T4 Gc, Ta= -25°C to +75°C (> +70°C derating)] Certificate No. EPS 12 ATEX 1 491 X |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU For DRB-24V020ABA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU |
| Galvanic Isolation (Input & Output / PE) | 1.5 KVac |
| Signal / PE | 1.5 KVac CliQ II Buffer Module 24 V 20 A / DRB-24V020AB□ EMC |
| Emissions (CE & RE) | Generic Standards: CISPR 32, EN/BS EN 55032, EN/BS EN 55011, FCC Title 47: Class B |
| Component Power Supply for General Use | EN 61204-3 |
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz-1 GHz, 10 V/M, 80% modulation (1 KHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter |
| Voltage Dips and Interruptions (IEC 61000-4-11) | Level 3 Criteria A 1) Additional 100% dip; 1 cycle (20 ms); No Damage |
| Low Energy Pulse Test (Ring Wave) (IEC 61000-4-12) | Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV |
| Harmonic Current Emission | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units. 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common (Line to earth) 3) Symmetrical: Differential mode (Line to line) CliQ II Buffer Module 24 V 20 A / DRB-24V020AB□ Block Diagram Device Description |
| 1) | Input / Output terminal block connector |
| 2) | Signal terminal block connector |
| 3) | Select switch (operation mode) |
| 4) | LED display status |
| 5) | Universal mounting rail system CliQ II Buffer Module 24 V 20 A / DRB-24V020AB□ Dimensions L x W x D: 121 x 70 x 120.1 mm (4.76 x 2.76 x 4.73 inch) Engineering Data |
| Output Load De-rating VS Surrounding Air Temperature | Note |