| Serie | CliQ III |
| Modell | DRP-24V120W1CAN |
| Typ | Hutschienen-Netzteile |
| Marke | DELTA |
| Fig. 1 | Fig. 2 Efficiency VS Output Load at 24 V |
| Fig. 3 | Fig. 4 Power Factor VS Output Load at 24 V CliQ III DIN Rail Power Supply 24 V 120 W 1 Phase / DRP-24V120W1C□N Output Ratings / Characteristics* |
| Nominal Output Voltage | 24 Vdc |
| Factory Set Point Tolerance | 24 Vdc ± 1.0% |
| Output Voltage Adjustment Range | 24-28 Vdc |
| Output Current (Nom.) | 0-5.0 A / 0-4.28 A Continuously operating at 24 V / 28 V |
| Nom. (7.5 A / 6.43 A) | Power Boost for 5 seconds at 24 V / 28 V, |
| (Slew rate 0.1 A/µs) | refer to the details in the Function section |
| Output Power (Nom.) | 120 W / 120 W Continuously operating at 24 V / 28 V |
| Nom. (180 W / 180 W) | Power Boost for 5 seconds at 24 V / 28 V, refer to the details in the Functions section |
| Power Boost Duration (Min.) | 5 seconds Duration after which output voltage start to droop. Refer to the details in the Function section at Overload & Overcurrent Protections |
| Power Boost Recovery Time (Typ.) | 18 seconds Required wait duration before next Power Boost can be delivered by the power supply. Refer to the details in the Function section |
| Advanced Power Boost (Typ.) | 10 A @ 50 ms, resistive load Output voltage will drop (Refer to the |
| Line Regulation (Max.) | 0.5% (@ 88-264 Vac input, 100% load) |
| Load Regulation (Max.) | 1.0% (@ 88-264 Vac input, 0-100% load) |
| PARD** (Max.) | 100 mVpp 20 Hz to 20 MHz, 50 Ohm, warm up for 5 mins *For power de-rating, see power de-rating on page 5. **PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor. |
| 115 Vac | 230 Vac |
| Rise Time (Max.) | 60 ms At 24 V, 5 A. |
| Start-up Time (Max.) | 1,500 ms At 24 V, 5 A. |
| Hold-up Time (Typ.) | 35 ms At 24 V, 5 A. |
| Min. (20 ms) | At 24 V, 5 A. |
| Dynamic Response (Max.) | ± 5% @ 0-100% load Slew rate 0.1 A/µs |
| (Overshoot & Undershoot O/P Voltage) | (@ 5 Hz, 50 Hz & 1 kHz, 50% Duty Cycle) |
| Start-up with Capacitive Loads (Max.) | 10,000 µF |
| Functional (DC OK Relay) | Rated: 30 V at 1 A, resistive load. Refer to the details in the Function |
| Contact | section at DC OK Relay Contacts and LED Indicator Characteristics on page 14. CliQ III DIN Rail Power Supply 24 V 120 W 1 Phase / DRP-24V120W1C□N Mechanical |
| Case Cover / Chassis | Aluminium |
| Indicator (Green LED) | DC OK |
| Cooling System | Convection |
| Terminal (Input) | 3 Pins (Rated 600 V / 35 A) |
| Signal | 2 Pins (Rated 300 V / 28 A) |
| Wire (Input) | AWG 18-8 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA Environment |
| Surrounding Air Temperature (Operating) | -25°C to +70°C (Cold start -40°C) |
| Storage | -40°C to +85°C |
| Power De-rating (Vertical) | > 60°C de-rate power by 2.5% / °C Mounting |
| Horizontal | > 40°C de-rate power by 1.67% / °C Mounting |
| Eingangsspannung | AC input < 100 Vac de-rate power by 0.83% / V DC input < 100 Vdc de-rate power by 1.67% / V |
| Betriebsfeuchtigkeit | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 30 G for a duration of 18 ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Sine Wave: 10-500 Hz; 3 G peak; displacement of 0.35 mm; 60 min per axis for all X, Y, Z directions |
| Bump Test (Operating) | IEC 60068-2-29, Half Sine Wave: 10 G for a duration of 11 ms, 1,000 times per direction, 6,000 times in total |
| Over Voltage Category | III (operating altitude 2,500 Meters) According to IEC/EN 62477-1 / II (operating altitude 5,000 Meters) EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) CliQ III DIN Rail Power Supply 24 V 120 W 1 Phase / DRP-24V120W1C□N Protections |
| Overvoltage (28.8 - 35.2 V, SELV Output,) | Refer to the details in the Function |
| Hiccup Mode, Non-Latching | section (Auto-Recovery) |
| current, Constant current, | section Hiccup Mode (Auto-Recovery) |
| Over Temperature (< 80°C Surrounding Air) | Refer to the details in the Function |
| Temperature @ 100% load, | section Non-Latching (Auto-Recovery) |
| Short Circuit (Hiccup Mode, Non-Latching) | Load impedance ≤ 100 mOhm, refer to (Auto-Recovery when the fault the details in the Function section is removed) |
| Transient Surge Voltage Protection | MOV (Metal Oxide Varistor) |
| Internal Fuse at L pin | T 3.15 A |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with PE* connection *PE: Primary Earth Reliability Data |
| MTBF (as per Telcordia SR-332) (1,411,300 hrs.) | I/P: 115 Vac, O/P: 24 V, 5 A, Ta: 25°C |
| 842,900 hrs. | I/P: 115 Vac, O/P: 24 V, 5 A, Ta: 40°C |
| Expected Cap Life Time** (131,400 hrs.) | O/P: 24 V, 5 A, Ta: 25°C |
| 131,400 hrs. | O/P: 24 V, 2.5 A, Ta: 40°C |
| 21,100 hrs. (32,700 hrs.) | O/P: 24 V, 5 A, Ta: 60°C |