| Série | DIN Eco |
| Modelo | DRL-24V120W3EN |
| Tipo | Fontes de alimentação em trilho DIN |
| Marca | DELTA |
| Case Chassis | Aluminum |
| Case Cover | SGCC |
| Dimensions (H x W x D) | 123.6 x 40 x 116.8 mm (4.87 x 1.57 x 4.60 inch) |
| Indicator (Green LED) | DC OK |
| Cooling System | Convection |
| Terminal*4 (Input) | 4 Pins (Rated 600 V / 30 A) |
| Wire (Input) | AWG 18-10 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25dBA *4 The torque at the screw terminal connector shall not exceed 8.0 Kgf.cm. (7.0 lbf.in). Environment |
| Surrounding Air (Operating) | -40°C to +70°C |
| Temperature *5/6 | (Please refer to page 8 derating curve) |
| Storage | -40°C to +85°C |
| Power De-rating (Temperature) | > 50°C de-rate power by 2.5 % / °C |
| Umidade de operação | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-64, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction |
| Operating | IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s² (2 G peak); 10 min per cycle, 60 min for X, Y, Z direction |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2,000 meters altitude) *5 When operating at temperatures below -30°C, the PSU may require a few seconds to “bounce” before completing a cold-start power-up. *6 For power de-rating from 50°C to 70°C, see power de-rating on page 8. DIN Eco Series DIN Rail Power Supply 120 W 3-Phase / DRL-V120W3EN Protections |
| Overvoltage | < 68 V, SELV Output, Auto-recovery Mode |
| Overload / Overcurrent | 105 – 165% of rated load current, Auto-recovery (150% Power Boost for 500 ms) |
| Over Temperature | Non-Latching (Auto-recovery) |
| Curto-circuito | Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed) |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with PE*7 connection *7 PE: Primary Earth Reliability Data |
| MTBF (Telcordia) | > 700,000 hrs. |
| Expected Cap Life Time (10 Years) | I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 50% load, Ta: 40°C |
| Warranty (3 Years) | I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 80% load, Ta: 50°C Safety Standards / Directives |
| Electrical Safety (CB scheme) | IEC/EN/BS EN 62368-1, AS/NZS 62368-1; IEC/EN 61010-1/-2-201 |
| TUV Bauart | IEC/EN 62368-1 |
| UL/cUL | UL 62368-1, CSA C22.2; UL 61010-1/-2-201, CAN/CSA-C22.2 No. 61010-1-12 |
| CCC | GB4943.1 |
| BIS | IS 13252-1 (Part 1) |
| BSMI | CNS 15598-1 |
| EAC | TP TC 004/2011 |
| KC | KC 62368-1 (upon request) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| SELV | IEC/EN 61010-1/2-201, IEC/EN 62368-1 |
| Galvanic Isolation*8 (Input to) | 4.0 kVac Output |
| Input to | 2.5 kVac Ground |
| Output to | 0.5 kVac Ground *8 For Hi-Pot testing, the Gas tube screw of TM200 must be removed, after testing must be reinstalled the screw. DIN Eco Series DIN Rail Power Supply 120 W 3-Phase / DRL-V120W3EN EMC*9 |
| Emissions (CE & RE) | CISPR 32, EN/BS EN 55032, AS/NZS CISPR 32, Class B; KS C 9832; CNS15936; EN/EN BS 61000-6-4, EN/BS EN 61204-3; Compliance to FCC Title 47 |
| Immunity | EN/BS EN 55035; KS C 9835; EN/BS EN 61000-6-2 ; EN/BS EN 61204-3 |
| Electrostatic (IEC 61000-4-2) | Level 4 Criteria A1) |
| Discharge | Air Discharge: 15k V Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Criteria A1) 80 MHz – 1 GHz, 10 V/M, 80% Modulation (1 kHz) 1.4 GHz – 6 GHz, 3 V/M, 80% Modulation (1 kHz) 2 GHz – 2.7 GHz, 1 V/M, 80% Modulation (1 kHz) |
| Electrical Fast (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV Transient / Burst |
| Surge (IEC 61000-4-5) | Level 4 Criteria A1) |
| Condition | W/O SPD |
| Common Mode3) | 4 kV |
| Differential Mode4) | 2 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) |
| Susceptibility | 150 kHz – 80 MHz, 10 Vrms |
| Power Frequency (IEC 61000-4-8) | Level 4 Criteria A1) |
| Magnetic Fields | 30 A/m |
| Voltage Dips and (IEC 61000-4-11) | 0% residual; 1 cycle, Criteria A1) |
| Interruptions | 40% residual; 10 cycle, Criteria B1) 70% residual; 25 cycle, Criteria B1) Harmonic Current IEC/EN/EN BS 61000-3-2, Class A Emission Voltage |
| Fluctuation and | IEC/EN/EN BS 61000-3-3, dmax ≤ 4% Flicker |
| Voltage Sag (80% of 380 Vac) | 304 Vac, 1,000 ms Criteria A1) |