| Série | PJL |
| Modèle | PJL-48V200WBAA |
| Marque | DELTA |
| Cooling System (Convection) | 0-150 W |
| Fan Cool | 151-200 W With 400 LFM fan cool, 15mm distance between PSU and fan |
| Power Supply Header (Input (CN1)) | 1-1123724-3 |
| Output (CN2) | 1-1123723-4 |
| Wire (Input (CN1)) | AWG 18 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA Environment |
| Surrounding Air Temperature (Operating) | -40°C to +70°C |
| Storage | -40°C to +85°C |
| Power De-rating (Temperature) | > 50°C de-rate power by 3.75 W / °C |
| (Convection) | (150 W @ 50°C, 112.5 W @ 60°C, 75 W @ 70° C) |
| Temperature | > 50°C de-rate power by 5 W / °C |
| Tension d’entrée | < 100 Vac de-rate power by 1.33% / Vac (80% load at 85 Vac) |
| Cold Temperature | < -20°C de-rate power by 2W / °C (80% load at -40°C) |
| Operating and Storage Humidity | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine 50 G for a duration of 11 ms, 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10 Hz to 150 Hz @ 25 m/S² (2.5 G peak); displacement of 0.35 mm; 90 min per axis for all X, Y, Z direction |
| Over Voltage Category | II Protections |
| Output Overvoltage | < 60 V, SELV Output, Latch Mode |
| Input Under Voltage | Brownout & Brownout Recovery protection |
| Overload / Overcurrent | > 105% of rated load current, Hiccup mode, Non-Latching (Auto recovery) |
| Over Temperature | Latch Mode |
| Court-circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Internal Fuse at L pin | T4AH |
| Protection Against Shock | Class I with PE* connection *PE: Primary Earth PJL Open Frame Power Supply 48 V 200 W 1 Phase / PJL-48V200WBAA Reliability Data |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 I/P: 115Vac, O/P: 100% load, Ta: 25°C |
| Expected Cap Life Time | 10 years (115 Vac & 230 Vac, 50% load @ 40°C) Safety Standards / Directives |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| Electrical Safety (SIQ Bauart) | EN 62368-1 |
| cCSAus | CSA C22.2 No. 250.13 and UL 8750 CSA C22.2 No. 60950-1 and UL 60950-1 CSA C22.2 No. 62368-1 and UL 62368-1 |
| CB scheme | IEC 60950-1, IEC 62368-1, IEC 61347-1 and IEC 61347-2-13 |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| UKCA | In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 |
| Galvanic Isolation (Input to Output) | 4 kVac (Reinforced) 3 kVac (Production Test) |
| Input to Ground | 1.5 kVac (Basic & Production Test) |
| Output to Ground | 1.5 kVac (Basic) |
| Isolation Resistance (Input to Output) | > 100 MOhm |
| PE Resistance | < 0.1 Ohm EMC |
| Emissions (CE & RE) | Generic Standards: CISPR 32, EN/BS EN 55032: Class B |
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 55035 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 3 Criteria A1) Air Discharge: 8 kV Contact Discharge: 6 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz-1 GHz, 10 V/M, 80% modulation (1 kHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV (Input power ports) |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) Common Mode3): 2 kV Differential Mode4): 1 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter |
| Voltage Dips and Interruptions (IEC 61000-4-11) | 100% dip; 1 cycle (20 ms); Self Recoverable |
| Low Energy Pulse Test (IEC 61000-4-12) | Level 3 Criteria A1) |
| (Ring Wave) | Common Mode3): 2 kV Differential Mode4): 1 kV |
| Harmonic Current Emission | IEC/EN/BS EN 61000-3-2, Class C |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 at nominal voltages and full 1) Criteria A: Normal performance within the specification limits 3) Asymmetrical: Common mode (Line to earth) 2) Criteria B: Temporary degradation or loss of function which is self-recoverable 4) Symmetrical: Differential mode (Line to line) PJL Open Frame Power Supply 48 V 200 W 1 Phase / PJL-48V200WBAA Block Diagram PJL Open Frame Power Supply |
| 1. | Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1. |
| 2. | If the output capacity is not reduced when the surrounding air temperature exceeds its specification as defined on Page 3 under “Environment”, the device will run into Over Temperature Protection. When activated, power supply will latch off, until the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition, and require removal/re-application of input AC voltage in |
| 3. | In order for the device to function in the manner intended, it is also necessary to keep a safety distance as recommended in the safety instructions while the device is in operation. |
| 4. | Depending on the surrounding air temperature |
| Fig. 1 | and output load delivered by the power supply, the device can be very hot! |
| Temperature (Power De-rating) | 5. If the device has to be mounted in any other |
| Fan cool (orientation,) | please contact > 50°C de-rate power by 5 W / °C info@deltapsu.com for more details. (200 W @ 50°C, 150 W @ 60°C, 100 W @ 70°C) < -20°C de-rate power by 1% / °C (160 W @ -40°C) |
| Fig. 2 | Installation of the Device |
| Fig. 3 | Assembly Reference |