| Serie | LYTE II |
| Modelo | DRL-12V120W1EN |
| Tipo | Fuentes de alimentación en carril DIN |
| Marca | DELTA |
| Case Cover / Chassis | SGCC / Aluminum |
| Dimensions (H x W x D) | 123.6 x 30 x 116.8 mm (4.87 x 1.18 x 4.60 inch) |
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Terminal*4 (Input) | 3 Pins (Rated 300 V / 30 A) |
| Wire (Input) | AWG 18-12 (Current rating can refer to “AWG Wire Table”) |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA *4 The torque at the terminal connector shall not exceed 4 Kgf.cm. (3.47 lbf.in). Environment |
| Surrounding Air (Operating) | -40°C to +70°C |
| Temperature (Storage) | -40°C to +85°C |
| Power De-rating | > 40°C de-rate power by 1.67 % / °C @ 115 Vac |
| Temperature | > 50°C de-rate power by 2.5 % / °C @ 230 Vac Input |
| Voltage | < 100 Vac de-rate power by 1% / Vac |
| Humedad de funcionamiento | 20 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-) | IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, |
| Operating | 9 times in total |
| Vibration (Non-) | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) LYTE II DIN Rail Power Supply DRL-120W series / DRL-V120W1EN Protections |
| Overvoltage (< 17.4 V, SELV Output,) | < 33.6 V, SELV Output, < 64.8 V, SELV Output, |
| Latch Mode (Latch Mode) | Latch Mode |
| Overload / Overcurrent | 105 - 150% of rated load current, Auto-recovery Continuous current limit Mode*5 (Vo > 80%) |
| Over Temperature | Latch Mode |
| Cortocircuito | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Internal Fuse at L pin | T4 A / 250 V |
| Protection Against Shock | Class I with PE*6 connection *5 Constant current limit protection for inductive and capacitive load applications *6 PE: Primary Earth Reliability Data |
| MTBF (Telcordia) | > 700,000 hrs |
| Expected Cap Life Time | 10 years (230 Vac, 50% load @ 40°C) Safety Standards / Directives |
| Electrical Safety (CB scheme) | IEC 62368-1, IEC 61010-1 & -2-201 |
| TUV Bauart | EN 62368-1, EN 61010-1 & -2-201 |
| UL/cUL | UL 62368-1, UL 61010-1 & -2-201 |
| BIS | IS 13252-1 (Part 1) |
| BSMI | CNS14336-1 |
| CCC | GB4943.1 |
| EAC | TP TC 004/2011 |
| KC | K 60950-1 (24 V model only) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 and Electromagnetic Compatibility Regulations 2016 |
| Galvanic Isolation | Input to 3.0 KVac Output Input to 2.0 KVac Ground Output to 1.0 KVac Ground LYTE II DIN Rail Power Supply DRL-120W series / DRL-V120W1EN EMC |
| Emissions (CE & RE) | CISPR 32, EN/BS EN 55032, EN/BS EN 61000-6-4, AS/NZS CISPR32, EN/BS EN 61204-3, KN 32 (24 V model only) Compliance to FCC Title 47, EN/BS EN 61000-6-3: Class B Component Power |
| Supply for General Use | EN/BS EN 61204-3 |
| Immunity | EN/BS EN 55035, KN 35 (24 V model only), EN/BS EN 61000-6-2 Compliance to EN/BS EN 61000-6-1 |
| Electrostatic (IEC 61000-4-2) | Level 4 Criteria A1) |
| Discharge | Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Criteria A1) 80 MHz – 1 GHz, 10 V/M, 80% Modulation (1 kHz) 1.4 GHz – 2 GHz, 3 V/M, 80% Modulation (1 kHz) 2 GHz – 2.7 GHz, 1 V/M, 80% Modulation (1 kHz) |
| Electrical Fast (IEC 61000-4-4) | Level 3 Criteria A1) |
| Transient / Burst | 2 kV |
| Surge (IEC 61000-4-5) | Level 4 Criteria A1) Common Mode4): 4 kV Differential Mode5): 2 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz – 80 MHz, 10 Vrms |
| Power Frequency (IEC 61000-4-8) | Level 4 Criteria A1) |
| Magnetic Fields | 30 A/m |
| Voltage Dips and (IEC 61000-4-11) | 0% residual; 1 cycle, Criteria B2) |
| Interruptions | 40% residual; 10 cycle, Criteria C3) 70% residual; 25 cycle, Criteria C3) Harmonic Current |
| Emission | IEC/EN/BS EN 61000-3-2, Class A Voltage Fluctuation and |
| Flicker | IEC/EN/BS EN 61000-3-3 |
| Voltage Sag Immunity (80% of 200 Vac) | 160 Vac, 1000 ms Criteria A1) |
| SEMI F47 – 0706 (70% of 200 Vac) | 140 Vac, 500 ms Criteria A1) |
| 50% of 200 Vac (100 Vac, 200 ms) | Criteria A1) 1) Criteria A: Normal performance within the specification limits 2) Criteria B: Temporary degradation or loss of function which is self-recoverable 3) Criteria C: Output out of regulation, shuts down during test (Need to recycle AC power cord to normal operation after test) 4) Asymmetrical: Common mode (Line to earth) 5) Symmetrical: Differential mode (Line to line) LYTE II DIN Rail Power Supply |
| 1) | Input terminal block connector |
| 2) | Output terminal block connector |