| Serie | SYNC |
| Modell | DRS-12V50W1NR |
| Typ | Hutschienen-Netzteile |
| Marke | DELTA |
| Case Cover / Chassis | Plastic |
| Indicator (Green LED) | DC OK |
| Cooling System | Convection |
| Terminal (Input) | 3 Pins (Rated 300 V/16 A) |
| Wire (Input / Output) | AWG 22-12 / AWG 20-12 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 25 dBA Environment |
| Surrounding Air Temperature (Operating) | -20°C to +70°C (Cold start at -40°C @ 40% load) |
| Storage | -40°C to +85°C |
| Power De-rating | -10°C to -20°C de-rate power by 2% / °C > 55°C de-rate power by 3.33% / °C |
| Betriebsfeuchtigkeit | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 2,000 Meters (6,560 ft.) |
| Shock Test (Non-Operating) | IEC60068-2-27, Half Sine Wave: 50 G for a duration of 11 ms; 3 times per direction, 9 times in total |
| Operating | IEC 60068-2-27, Half Sine Wave: 10 G for a duration of 11 ms; 1 time in X axis |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5-500 Hz; 2.09 Grms, 20 min per axis for all X, Y, Z directions |
| Over Voltage Category | II Protections |
| Overvoltage | < 18.7 V, SELV Output, Latch Mode |
| Overload / Overcurrent | 105~120% of rated load current, Foldback Mode (continuous current, voltage drops), Auto-recovery when the fault is removed |
| Over Temperature | < 75°C Surrounding Air Temperature @ 100% load, Latch Mode |
| Kurzschluss | Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed) |
| Internal Fuse at L pin | T3.15A |
| Degree of Protection | IP20 |
| Protection Against Shock | Class I with PE* connection *PE: Primary Earth Sync DIN Rail Power Supply 12 V 50 W 1 Phase (NEC Class 2) / DRS-12V50W1N□ Reliability Data |
| MTBF (Telcordia SR-332) | > 700,000 hrs I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C O/P: 100% load, Ta: 25°C |
| Expected Cap Life Time | 10 years (115 ac & 230 Vac, 50% load @ 40°C) Safety Standards / Directives |
| Safety Entry Low Voltage | SELV (IEC 60950) |
| Electrical Safety (TUV Bauart) | EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CB Scheme | IEC 60950-1, IEC 62368-1, Limited Power Source (LPS) |
| UKCA | BS EN 62368-1 |
| Industrial Control Equipment (UL/cUL listed) | UL 508 and CSA C22.2 No. 107.1-01 (File No. E315335) |
| Class 2 Power Supply (UL/cUL recognized) | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation (Input to Output) | 3.0 KVac |
| Input to Ground | 3.0 KVac |
| Output to Ground | 0.5 KVac Sync DIN Rail Power Supply 12 V 50 W 1 Phase (NEC Class 2) / DRS-12V50W1N□ EMC |
| Emissions (CE & RE) | Generic Standards: EN/BS EN 61000-6-3, EN/BS EN 61000-6-4, CISPR 32, EN/BS EN 55032, EN/BS EN 55011, FCC Title 47: Class B |
| Component Power Supply for General Use | EN 61204-3 |
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-1, EN/BS EN 61000-6-2 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 3 Criteria A1) Air Discharge: 8 kV Contact Discharge: 6 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz - 1 GHz, 10V/M with 1 kHz tone / 80% modulation 1.4 GHz - 2 GHz, 3 V/M with 1 kHz tone / 80% modulation 2 GHz - 2.7 GHz, 1 V/M with 1 kHz tone / 80% modulation |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) Common Mode3): 2 kV Differential Mode4): 1 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 30 A/Meter |
| Voltage Dips and Interruptions (IEC 61000-4-11) | 0% of 100 Vac, 20 ms Criteria A1) |
| 0% of 100 Vac, 5000 ms | Criteria B2) |
| 40% of 100 Vac, 200 ms | Criteria B2) |
| 70% of 100 Vac, 10 ms | Criteria A1) |
| 70% of 100 Vac, 500 ms | Criteria B2) |
| 0% of 240 Vac, 20 ms | Criteria A1) |
| 0% of 240 Vac, 5000 ms | Criteria B2) |
| 40% of 240 Vac, 200 ms | Criteria A1) |
| 70% of 240 Vac, 500 ms | Criteria A1) |
| Low Energy Pulse Test (Ring Wave) (IEC 61000-4-12) | Level 3 Criteria A1) Common Mode3): 2 kV Differential Mode4): 1 kV |
| Harmonic Current Emission | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 1) Criteria A: Normal performance within the specification limits 2) Criteria B: Temporary degradation or loss of function which is self-recoverable 3) Asymmetrical: Common mode (Line to earth) 4) Symmetrical: Differential mode (Line to line) Sync DIN Rail Power Supply 12 V 50 W 1 Phase (NEC Class 2) / DRS-12V50W1N□ Block Diagram DRS-12V50W1NZ DRS-12V50W1NR Sync DIN Rail Power Supply |
| 1) | Input terminal block connector |
| 2) | Output terminal block connector |
| 3) | DC voltage adjustment potentiometer |