| Série | CliQ II DC-UPS Module |
| Modelo | DRU-24V40ABN |
| Tipo | Acessórios |
| Marca | DELTA |
| Current (7.5 AH) | 12 AH 15 AH |
| 2.5 A (6,500 s) | 14,500 s 19,000 s |
| 5A (3,000 s) | 7,000 s 9,000 s |
| 10 A (1,200 s) | 2,400 s 3,200 s |
| 20 A (400 s) | 1,100 s 1,500 s |
| 30 A (120 s) | 450 s 600 s |
| 40 A (25 s) | 200 s 280 s |
| Fig. 1 | Buffering Time VS. Output Current Mechanical |
| Case Cover / Chassis | Aluminium |
| LED Indicator (Green LED) | DC OK, Battery Charging (flash) |
| Red LED | Battery Fail |
| Orange LED | Reverse polarity, Battery Discharging (flash) |
| Cooling System | Convection |
| Terminal (Input & Output / Battery) | 4 Pins (Rated 600 V/60 A) |
| Signal | 6 Pins (Rated 300 V/27 A) |
| Wire (Input & Output / Battery) | AWG 12-6 Load: 0-20 A |
| AWG 8-6 | Load: 20-40 A |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 40 dBA CliQ II DC-UPS Module 24 V 40 A / DRU-24V40ABN Environment |
| Surrounding Air Temperature (Operating) | -20°C to +60°C (full power) |
| Storage | -40°C to +85°C |
| Umidade de operação | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 3,000 Meters (9,840 ft) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 30 G (300 m/S²) for a duration of 18 ms, 1 time per direction, 2 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/S² (3 G peak); 60 min per axis for all X, Y, Z direction Protections |
| Overvoltage (Buffering Mode) | 29.5-30.5 V will not cause damage to the unit, Latch Mode |
| Overload / Overcurrent (Buffering Mode) | 42-52 A, Latch Mode |
| Over Temperature (Buffering Mode) | < 90°C Surrounding Air Temperature inside the unit, Latch Mode |
| Short Circuit (at system) (Buffering Mode) | Shutdown, Latch Mode |
| Input Polarity Protection* | Yes (DC OK = open contact, LED Status = Orange) |
| Battery Polarity Protection* | Yes (DC OK = open contact, LED Status = Orange) |
| Wrong Battery Voltage Protection | Yes, 30 Vdc Max (the maximum voltage that will not cause damage to the unit) |
| Deep Discharge Protection | Yes (23 V ± 0.5 V)** |
| Degree of Protection | IP 20 |
| Protection Against Shock | Class III **The unit will stop operating when the battery voltage detected is less than 23 V ± 0.5 V. Reliability Data |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 CliQ II DC-UPS Module 24 V 40 A / DRU-24V40ABN Safety Standards / Directives |
| Electrical Equipment of Machines | EN/BS EN 60204-1 |
| Electrical Equipment for Use in Electrical Power Installations | IEC/EN/BS EN 62477-1 / IEC 62103 |
| Safety Entry Low Voltage | SELV (EN 60950-1) PELV (EN 60204-1, EN 62477-1) |
| Electrical Safety (SIQ Bauart) | EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CB scheme | IEC 60950-1, IEC 62368-1 |
| KC | K 60950-1 |
| UKCA | BS EN 62368-1 |
| Industrial Control Equipment (UL/cUL listed) | UL 508 and CSA C22.2 No. 107.1-16 (File No. E315355) |
| CSA | CSA C22.2 No. 107.1-16 (File No. 181564) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation (Power Port to Housing) | 1.0 KVac |
| Signal Port to Housing | 1.0 KVac |
| Power Port to Signal Port | 1.0 KVac EMC |
| Emissions (CE & RE) | Generic Standards: CISPR 32, EN/BS EN 55032, KN32, EN/BS EN 55011, FCC Title 47: Class B |
| Component Power Supply for General Use | EN/BS EN 61204-3 |
| Immunity | Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-2 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz-1 GHz, 10 V/M, 80% modulation (1 KHz) 1.4 GHz-2 GHz, 3 V/M, 80% modulation (1 KHz) 2 GHz-2.7 GHz, 1 V/M, 80% modulation (1 KHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV (Input power ports) |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) 0.5 kV (Input power ports) |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter 1) Criteria A: Normal performance within the specification limits CliQ II DC-UPS Module 24 V 40 A / DRU-24V40ABN Block Diagram Device Description |
| 1) | Input & Output / Battery terminal block connector |