| Serie | Chrome DC-UPS Module |
| Modelo | DRU-24V10ACZ |
| Tipo | Accesorios |
| Marca | DELTA |
| Current (3.3 AH) | 7.5 AH 12 AH |
| 0.5 A (400) | 900 1400 |
| 1A (180) | 398 654 |
| 2A (70) | 165 323 |
| 4A (28) | 72 160 |
| 6A (19) | 55 103 |
| 8A (11) | 22 49 |
| 10 A (7) | 18 37 |
| Fig. 1 | Buffering Time VS. Output Current Mechanical |
| Case Cover / Chassis | Plastic |
| Dimensions (H x W x D) | 91.0 x 71.0 x 55.6 mm (3.58 x 2.80 x 2.19 inch) |
| LED Indicator (Green LED) | DC OK, Battery Charging (flash) |
| Red LED | Battery Fail |
| Orange LED | Reverse polarity, Battery Discharging (flash) |
| Cooling System | Convection |
| Terminal (Input / Output / Battery) | 6 Pins (Rated 300 V/25 A) |
| Signal | 6 Pins (Rated 300 V/25 A) |
| Wire (Input / Output / Battery) | AWG 14-12 |
| Mounting Rail | Standard TS35 DIN Rail in accordance with EN 60715 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 40 dBA Chrome DC-UPS Module 24 V 10 A / DRU-24V10ACZ Environment |
| Surrounding Air Temperature (Operating) | -20°C to +60°C (full power) |
| Storage | -25°C to +85°C |
| Humedad de funcionamiento | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 3,000 Meters (9,840 ft.) |
| Shock Test (Operating) | IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22 ms, 3 time per direction, 9 times in total |
| Non-Operating | IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11 ms, 3 time per direction, 9 times in total |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions |
| Overvoltage (Buffering Mode) | 33 Vdc Max will not cause damage to the unit, Latch Mode |
| Overload / Overcurrent (Buffering Mode) | < 18 A, Latch Mode |
| Over Temperature (Buffering Mode) | < 90°C Surrounding Air Temperature inside the unit, Latch Mode |
| Short Circuit (at system) (Buffering Mode) | Shutdown, Latch Mode |
| Input Polarity Protection* | Yes (DC OK = open contact, LED Status = Orange) |
| Battery Polarity Protection* | Yes (DC OK = open contact, LED Status = Orange) |
| Wrong Battery Voltage Protection | Shutdown, 35 V Max (the maximum voltage that will not cause damage to the unit) |
| Deep Discharge Protection | Yes (22 V ± 1 V)** |
| Degree of Protection | IP 20 |
| Protection Against Shock | Class III ** The unit will stop operating when the battery voltage detected is less than 22V ± 1V Reliability Data |
| MTBF | > 500,000 hrs. as per Telcordia SR-332 Chrome DC-UPS Module 24 V 10 A / DRU-24V10ACZ Safety Standards / Directives |
| Electrical Equipment of Machines | EN BS EN 60204-1 |
| Electrical Equipment for Use in Electrical Power Installations | IEC/EN BS EN 62477-1 / IEC 62103 |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| Electrical Safety (SIQ Bauart) | EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CB scheme | IEC 60950-1, IEC 62368-1 |
| UKCA | BS EN 62368-1 |
| Industrial Control Equipment (UL/cUL listed) | UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) |
| BIS | IS 13252-1 |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation (Power Port to Signal Port) | 1.0 KVac EMC |
| Emissions (CE & RE) | Generic Standards: CISPR 32, EN/BS EN 55032, EN/BS EN 55011, FCC Title 47: Class B |
| Component Power Supply for General Use | EN/BS EN 61204-3 |
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz-1 GHz, 10 V/M, 80% modulation (1 KHz) 1.4 GHz-2 GHz, 3 V/M, 80% modulation (1 KHz) 2 GHz-2.7 GHz, 1 V/M, 80% modulation (1 KHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV (Input power ports) |
| Surge (IEC 61000-4-5) | Level 2 Criteria A1) 0.5 kV (Input power ports) |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter 1) Criteria A: Normal performance within the specification limits Chrome DC-UPS Module 24 V 10 A / DRU-24V10ACZ Block Diagram Device Description |
| 1) | Input / Output / Battery terminal block connector |
| 2) | Signal terminal block connector |