| Серия | DIN Pro Redundancy Module |
| Модель | DRR-80AF |
| Тип | Аксессуары |
| Бренд | DELTA |
| Surrounding Air Temperature (Operating) | -40°C to +80°C |
| Storage | -40°C to +85°C |
| Power De-rating (Vertical Mounting) | > 70°C de-rate power by 3% / °C |
| Horizontal Mounting | > 70°C de-rate power by 3% / °C |
| Рабочая влажность | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5000 Meters (16,666 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-64, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction |
| Operating | IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz (2G peak); 10 min per cycle, 60 min for X, Y, Z direction |
| Class of Equipment (Class III) | According to IEC/EN 62368-1 Protections Overload / Overcurrent*2 12 V / 24 V: 80 A < 160 A, No Damage |
| 48 V: 50 A | < 100 A, No Damage Short Circuit 12 V / 24 V: 80 A < 160 A, No Damage |
| Degree of Protection | IP20 |
| Protection Against Shock | Class III with PE*3 connection channel. *3 PE: Case earth Reliability Data |
| MTBF | > 800,000 hrs. as per Telcordia SR-332 I/P: 24 Vdc and 48 Vdc, O/P: 100% load, Ta: 25°C |
| Warranty | 3 Years DIN Pro Series Redundancy Module 80 A / DRR-80AF Safety Standards / Directives |
| Electrical Safety (CB Scheme) | IEC/EN 62368-1, AS/NZS 62368.1 RCM; IEC 61010-1/2-201 |
| UL/cUL Recognized | UL 62368-1 and CAN/CSA C22.2 No. 62368-1 (File No. E131881) |
| TUV | EN/IEC 62368-1 |
| UKCA | BS EN 62368-1 |
| EAC | TP TC 020/2011 |
| Industrial Control Equipment (UL/cUL Listed) | UL 61010-1/2-201 and CAN/CSA C22.2 No. 61010-1/2-201 (File No. E338991) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| ATEX (Zone 2) | II 3 G Ex ec nC IIC Gc EN IEC 60079-0:2018 EN IEC 60079-7:2015/A1:2018 EN IEC 60079-15:2019 |
| Galvanic Isolation (Input to PE) | 1.5 KVac |
| Output to PE | 1.5 KVac |
| Input/Output to DC OK | 0.5 KVac EMC |
| Emissions (CE & RE) | CISPR 32, EN/BS EN 55032 Class B AS/NZS CISPR 32 Class B / KS C 9832 |
| Immunity | EN/BS EN 55035 KS C 9835 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 KV Contact Discharge: 8 KV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz – 1 GHz, 3 V/M, 80% modulation (1 kHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 1 kV /5K HZ |
| Surge (IEC 61000-4-5) | Level 3 Criteria B1) Common Mode2): 2 KV Differential Mode3): 1 KV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz – 80 MHz, 3 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 30 A/Meter Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units. 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common (Line to earth) 3) Symmetrical: Differential mode (Line to line) DIN Pro Series Redundancy Module 80 A / DRR-80AF Block Diagram Device Description |
| 1) | Input terminal block connector |
| 2) | Output terminal block connector |
| 3) | DC OK relay contact |
| 4) | LED indicator of Vin1 & Vin2 |
| 5) | Earth connection |
| 6) | Universal mounting rail system DIN Pro Series Redundancy Module 80 A / DRR-80AF Dimensions H x W x D: 124.2 x 44 x 126.9 mm (4.88 x 1.73 x 4.99 inch) *Unless otherwise specified tolerance of dimension are ±1 mm Item Device Description Pin 1: V+ (V1) Pin 2: V- (V1) Pin 3: V+ (V2) Pin 4: V- (V2) Pin 5: V+ Pin 6: V- Pin 7: DC OK + (V1) Pin 8: DC OK - (V1) Pin 9: DC OK + (V2) Pin 10: DC OK - (V2) Wiring Size: |
| Stranded / Solid (Torque) | Stripping Length |
| (mm²) ((AWG)) | (Kgf.cm) (lbf.in) (mm) |
| (1) Input (8.37) | 8 14.0 12.2 11 |
| (2) Output (21.15) | 4 42.0 36.5 18 |
| (3) DC OK relay contact (0.32) | 22 - - 12 DIN Pro Series Redundancy Module 80 A / DRR-80AF Engineering Data |
| Output Load De-rating VS Surrounding Air Temperature | Note |
| 110 (1.) | The unit may degrade, or be damaged, when it is continuously used outside the shaded Percentage of Max Load (%) |
| 90 (2.) | If the output capacity is not reduced when the specification as defined on Page 3 under |
| 10 (4.) | Depending on the surrounding air temperature |
| -40 (-30) | -20 -10 0 10 20 30 40 50 60 70 80 supply, the device can be very hot! |
| Surrounding Air Temperature (°C) (5.) | If the device has to be mounted in any other orientation, please leave a message via the Contact Us form. |
| Fig. 1 | De-rating for Vertical and Horizontal Mounting Orientation > 70°C de-rate power by 3% / °C Output Load De-rating VS Input Voltage Load (W) |
| 12 (24) | 30 48 56 60 Input Voltage (Vdc) |
| Fig. 2 | De-rating for 31V-60V DC input with 40A-80A DIN Pro Series Redundancy Module 80 A / DRR-80AF Assembly & Installation The unit can be mounted on 35 mm (1.38 inch) DIN rails in accordance with EN 60715. The device should be installed with input terminal block at the top. Each device is delivered ready to install. |
| Mounting | Dismounting |
| Fig. 3.1 Mounting | Fig. 3.2 Dismounting Snap on the DIN rail as shown in Fig. 3.1: To uninstall, pull or slide down the latch with screw driver as shown 1. Tilt the unit upwards and insert it onto the DIN rail. in Fig. 3.2. Then slide the unit in the opposite direction, release the |
| 2. Push downwards until stopped. | latch and pull out the unit from the rail. 3. Press against the bottom front side for locking. 4. Shake the unit slightly to ensure that it is secured. In accordance to IEC/EN/UL 62368-1 and IEC/UL 61010-2-201, flexible cables require ferrules. Use appropriate copper cables that are designed to sustain operating temperature of 105°C or more to fulfill UL requirements. DIN Pro Series Redundancy Module |
| Fig. 4.1 1+1 Redundancy | Fig. 4.2 Single Use |
| Using 1 more PSU as the redundant unit. | Using more PSUs as the redundant units to increase the reliability. Fig. 4.3 N+1 Redundancy Connecting only one PSU to one DRR module to reduce the stress of the MOSFET and hence increase the reliability. DIN Pro Series Redundancy Module 80 A / DRR-80AF Operating Mode In order to ensure proper redundant operation for the power supply unit (PSU), the output voltage difference between the two units must |
| Fig. 5 | Redundant / Parallel Operation Connection Diagram Step 1. Measure output voltage of PSU 1 and PSU 2. If PSU 1 will be the master unit, then VO of PSU 1 must be higher than PSU 2. In order to set the output voltage, individually connect the power supply to 50% of rated load at any line voltage, and set the PSU 1 and PSU 2 output voltage. If it operate for 50% / 50% redundant condition then output must be kept within ±25 m v of output. |