| Серия | CliQ II Redundancy Modules |
| Модель | DRR-20A |
| Тип | Аксессуары |
| Бренд | DELTA |
| Surrounding Air Temperature (Operating) | -40°C to +80°C |
| Storage | -40°C to +85°C |
| Power De-rating (Vertical Mounting) | > 50°C de-rate power by 2.5% / °C |
| Horizontal Mounting | > 50°C de-rate power by 2.5% / °C |
| Рабочая влажность | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 2,500 Meters (8,200 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 30 G (300 m/s²) for a duration of 18 ms, 1 time per direction, 2 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/s² (3 G peak); 60 min per axis for all X, Y, Z direction |
| Over Voltage Category (III) | According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) Protections |
| Overload / Overcurrent* (DRR-20☐) | < 25 A, No Damage |
| Short Circuit (DRR-20☐) | < 25 A, No Damage |
| Degree of Protection | IP20 |
| Protection Against Shock | Class III with PE** connection module). **PE: Primary Earth Reliability Data |
| MTBF | > 800,000 hrs. as per Telcordia SR-332 I/P: 24 Vdc and 48 Vdc, O/P: 100% load, Ta: 25°C CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Safety Standards / Directives |
| Electrical Equipment of Machines | EN/BS EN 60204-1 (over voltage category III) |
| Electrical Equipment for Use in Electrical Power Installations | IEC/EN/BS EN 62477-1 / IEC 62103 |
| Electrical Safety (SIQ Bauart) | EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) |
| CB scheme | IEC 60950-1, IEC 62368-1 |
| UKCA | BS EN 62368-1 |
| Industrial Control Equipment (UL/cUL recognized) | UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) |
| Hazardous Location / ATEX (cCSAus) | CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007 |
| (For DRR-20A and DRR-40A) | [Class I, Division 2, Group A, B, C, D T4, Ta= -40°C to +80°C (> +50°C derating)] |
| ATEX | II 3G Ex nA nC IIC T4 Gc, Ta= -40°C to +80°C (> +50°C derating)] Certificate No. EPS 12 ATEX 1 491 X |
| KC | K 60950-1 (DRR-40N only) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU For DRR-20A and DRR-40A: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU |
| Galvanic Isolation (Input & Output / PE) | 1.5 KVac CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ EMC |
| Emissions (CE & RE) | Generic Standards: CISPR 32, EN/BS EN 55032, KN 32 (DRR-20N and DRR-40N only), EN/BS EN 55011, FCC Title 47: Class B |
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 KN 35 (DRR-20N and DRR-40N only) |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz – 1 GHz, 10 V/M, 80% modulation (1 kHz) |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz – 80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter |
| Voltage Dips and Interruptions (IEC 61000-4-11) | Level 3 Criteria A 1) Additional 100% dip; 1 cycle (20 ms); No Damage |
| Low Energy Pulse Test (Ring Wave) (IEC 61000-4-12) | Level 3 Criteria A1) Common Mode2): 2 kV Differential Mode3): 1 kV Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units. 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common (Line to earth) 3) Symmetrical: Differential mode (Line to line) CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ |
| 1) | Input terminal block connector |
| 2) | Output terminal block connector |
| 3) | LED indicator of Vin1 & Vin2 |
| 4) | Universal mounting rail system |
| 5) | Earth connection CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Dimensions DRR-20☐ H x W x D: 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) *Unless otherwise specified tolerance of dimension are ±1 mm DRR-40☐ H x W x D: 121 x 50 x 122.1 mm (4.76 x 1.97 x 4.81 inch) *Unless otherwise specified tolerance of dimension are ±1 mm CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Engineering Data |
| Output Load De-rating VS Surrounding Air Temperature | Note |
| Fig. 1 | Contact Us form. > 50°C de-rate power by 2.5% / °C Assembly & Installation The unit can be mounted on 35 mm (1.38 inch) DIN rails in accordance with EN 60715. The device should be installed with input terminal block at the top. Each device is delivered ready to install. |
| Mounting | Dismounting |
| Fig. 2.1 Mounting | Fig. 2.2 Dismounting Snap on the DIN rail as shown in Fig. 2.1: To uninstall, pull or slide down the latch with screw driver as 1. Tilt the unit upwards and insert it onto the DIN rail. shown in Fig. 2.2. Then slide the unit in the opposite direction, |
| 2. Push downwards until stopped. | release the latch and pull out the unit from the rail. 3. Press against the bottom front side for locking. 4. Shake the unit slightly to ensure that it is secured. In accordance to UL 60950 and EN 62368 / UL 62368, flexible cables require ferrules. Use appropriate copper cables designed to sustain operating temperature of 60°C / 75°C or more to fulfill UL requirements. CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ |
| ◼ (Vertical Mounting) | ◼ Horizontal Mounting in mm mm o er |
| o er (l) | in e n an o le l mm in e n an o le in |
| mm (in) | mm in mm OFF, there is risk of explosion / severe damage. the device. Vertical Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 20 mm (0.79 inch) to other units. Horizontal Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 50 mm (1.97 inch) to other units. supply. Risk of burns! this time. For DRR-20A and DRR-40A: EN 60079-0 or EN 60079-15. |
| Fig. 3.1 1+1 Redundancy | Fig. 3.2 Single Use |
| Using 1 more PSU as the redundant unit. | Using more PSUs as the redundant units to increase the reliability. Fig. 3.3 N+1 Redundancy Connecting only one PSU to one DRR module to reduce the stress of the diodes and hence increase the reliability. CliQ II Redundancy Modules 20 A / DRR-20□, 40 A / DRR-40□ Operating Mode In order to ensure proper redundant operation for the power supply unit (PSU), the output voltage difference between the two units must be kept at 0.45~0.50 V for 24 V supplies. Follow |
| respectively | **The Signal GND in the DRR module is for the built-in LED and DC OK signals. The Output |
| GND terminals from t e t o | U’s o not nee to be onne te to t e ignal GND terminal Step 3. Connect the system load from Vout. Please note that output Fig. 4 Redundant / Parallel Operation Connection Diagram voltage Vout from DRR module will be = VO (output voltage of power supply) – Vdrop* (in DRR module). *Vdrop will vary from 0.60 V to 0.90 V (Typical 0.65 V) depending on the load current and surrounding air temperature. These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5 A + 2.5 A = 5 A or |
| Step 1. | Step 3. Set output load condition for both supplies at 50% and measure Connect PSU 1 and PSU 2 with the DRR module and measure |
| the output voltages. | at Vin 1 & Vin 2 to verify the voltage difference. Ensure the voltages are within ±25 mV. Step 2. Adjust output voltages to the same level or within ±25 mV Step 4. |
| difference. | Output voltage from DRR module Vout will be = VO (output voltage of power supply) – Vdrop* (in DRR module). CliQ II Redundancy Modules 20A / DRR-20□, 40A / DRR-40□ Others Conformal Coating The Protective Coating Technology Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including under device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circuit board. The |