| Serie | PMU |
| Modell | PMU-13V155WCBA |
| Typ | Geschlossene Schaltnetzteile |
| Marke | DELTA |
| V1 (B+) | V1 B+ Battery Input / Output Characteristics |
| Nominal Battery Voltage (12 Vdc) | 24 Vdc 2 x 12 Vdc SLA Sealed lead acid battery |
| Battery Voltage Range | Continuously 11.0 to 13.8 Vdc (nominal at 12 V) 22.0 to 27.6 Vdc (nominal at 24 V) Operating Maximum |
| 16 Vdc Max | 32 Vdc Max Allowed Voltage Battery Low |
| Voltage1) (11.5 Vdc typ.) | 22.5 Vdc typ. Minimum |
| Voltage2) (9.0 Vdc ± 0.5 Vdc) | 18.0 Vdc ± 0.5 Vdc |
| Battery Capacity | 3.3 AH/ 7 AH/ 12 AH/ 15 AH |
| Charging Time3) | 2-10 hrs @ charging current of 1.5 A |
| Buffering Time (Approx.1hrs 15mins for battery) | Approx.2hrs 30mins for battery |
| 12 V/15 AH | 24 V/15 AH |
| Recommended External Fuse for Battery | Automotive 30 A / 80 V FK3 type from Littelfuse, or similar, in the battery B+ path. The battery fuse protects the wires between the battery and the unit. |
| Battery Charging (Normal Mode) | CC-CV mode (constant current-constant voltage) |
| End-of-Charge Voltage | The unit always charges battery to a fixed voltage value Mechanical |
| Case Chassis / Cover | AL / SGCC |
| Dimensions (L x W x H) (Enclosed) | 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch) |
| L Frame | 178 x 96.5 x 37.5 mm (7.01 x 3.80 x 1.48 inch) |
| Unit Weight (Enclosed) | 0.60 kg (1.32 lb) |
| LED Indicator (Green LED) | DC OK |
| Red LED | Battery Connected in Reverse Polarity |
| Cooling System | Convection |
| Terminal | M3.5 x 7 Pins (Rated 300 V/15 A) |
| Signal | JST: XHP-4 (PMU-☐V155W☐CA) |
| Wire | AWG 16-14 |
| Noise (1 Meter from power supply) | Sound Pressure Level (SPL) < 30dBA 1) The voltage level of battery to enable “BAT Low” function, for PMU-☐V155W☐CA model only B+ and B- terminals; and, with input and output loads disconnected. discharged at. PMU Panel Mount Power Supply with Integrated DC-UPS PMU-155 W Series / PMU-□V155W□□A Buffering Times VS Output Load and Battery Capacity PMU-13V155W☐☐A |
| 700 (Current) | 3.3 AH 7 AH 12 AH 15 AH |
| 600 (1.1 A) | 166 m 352 m 604 m 755 m Buffering Time (min) |
| 3.3 A (55 m) | 117 m 201 m 252 m |
| 5.5 A (33 m) | 70 m 121 m 151 m |
| 7.7 A (24 m) | 50 m 86 m 108 m |
| 300 (9.9 A) | 18 m 39 m 67 m 84 m |
| 200 (11.0 A) | 17 m 35 m 60 m 76 m These buffering times assume the battery is fully charged to begin with |
| 1.1 (3.3) | 5.5 7.7 9.9 11 Output Current (A) |
| 7.5AH (12AH) | 15AH 15AH |
| Fig. 1 | Buffering Time VS Output Current (PMU-13V155W☐☐A) PMU-27V155W☐☐A 1,600 |
| 1,400 (Current) | 3.3 AH 7 AH 12 AH 15 AH Buffering Time (min) |
| 1,200 (0.55 A) | 330 m 700 m 1208 m 1510 m 1,000 |
| 1.1 A (165 m) | 350 m 604 m 755 m |
| 2.2 A (82 m) | 175 m 302 m 377 m |
| 600 (4.5 A) | 40 m 85 m 147 m 184 m |
| 400 (5.5 A) | 33 m 70 m 120 m 151 m |
| 0.55 (1.1) | 2.2 3.3 4.5 5.5 Output Current (A) |
| Fig. 2 | Buffering Time VS Output Current (PMU-27V155W☐☐A) PMU Panel Mount Power Supply with Integrated DC-UPS PMU-155 W Series / PMU-□V155W□□A Model Number |
| Surrounding Air Temperature (Operating) | -20°C to +70°C |
| Storage | -40°C to +85°C |
| Power De-rating (I/P: 90-132 Vac) | < 0°C to -20°C de-rate power by 2.25% / °C 50°C to 70°C de-rate power by 2.25% / °C |
| I/P: 180-264 Vac | < 0°C to -20°C de-rate power by 2.5% / °C 50°C to 70°C de-rate power by 2.5% / °C |
| Betriebsfeuchtigkeit | 5 to 95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, 30G (300 m/S²) for a duration of 18 ms,3 times per direction, 9 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, 10 Hz to 150 Hz @ 50 m/S² (5 G peak); displacement of 0.35 mm; 20 min per axis for all X, Y, Z direction |
| Bump (Operating) | IEC 60068-2-29, 10 G (100 m/S²) for a duration of 11 ms,1000 times per direction, 3000 times in total |
| Over Voltage Category | II Protections |
| Overvoltage (V1) | <18.5 V, SELV Output, <37.0 V, SELV Output, |
| Hiccup mode, | Hiccup mode, |
| Non-latching (Auto-Recovery) | Non-latching (Auto-Recovery) |
| B+ (16 Vdc Max will not cause) | 32 Vdc Max will not cause |
| damage to the unit | damage to the unit |
| Overload / Overcurrent (Normal Mode) | 105-150% of rated load current, Hiccup mode, Non-Latching (Auto-Recovery) |
| Buffering Mode (11.5-19.0 A, Latch mode) | 6.05-11.0 A, Latch mode |
| Over Temperature | Latch mode |