| السلسلة | PMF |
| الطراز | PMF-24V240WCGB |
| النوع | مزودات طاقة تبديلية مغلقة |
| العلامة التجارية | DELTA |
| Case Chassis | Aluminium |
| Case Cover | Aluminium |
| Dimensions (L x W x H) | 190 x 93 x 50 mm (7.48 x 3.66 x 1.97 inch) |
| Indicator | Green LED (DC OK) |
| Cooling System | Forced Cooling |
| Terminal (PMF-24V240WCG☐) | M3.5 x 7 Pins (Rated 300 V/20 A) |
| Wire | AWG 20-12 Environment |
| Surrounding Air Temperature (Operating) | -10°C to +70°C (Cold start at -20°C) |
| Storage | -25°C to +85°C |
| Power De-rating | > 50°C de-rate power by 2.5% / °C < 100 Vac de-rate power by 1.33% / 1 V |
| رطوبة التشغيل | 10-95% RH (Non-Condensing) |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine: 50 G for a duration of 11 ms, 3 shocks for each 3 directions |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 Grms); 20 min per axis for all X, Y, Z direction Protections |
| Overvoltage | 27.6-32.4 V, Latch Mode (AC power is recycled) |
| Overload / Overcurrent | 105-150%, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| قصر الدائرة | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with PE* connection *PE: Primary Earth Reliability Data |
| MTBF | > 700,000 hrs. as per Telcordia SR-332 I/P: 100 Vac, O/P: 100% load, Ta: 35°C |
| Expected Cap Life Time | 10 years (115 Vac & 230 Vac, 50% load @ 40°C) PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ Saf ety Standards / Directives |
| Safety Entry Low Voltage | SELV (EN 60950-1) |
| Electrical Safety (TUV Bauart) | EN 60950-1, EN 62368-1 |
| UL/cUL recognized | UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881) |
| CB scheme | IEC 60950-1, IEC 62368-1 |
| BIS | IS 13252 (Part 1) (for PMF-24V240WCGB) |
| CCC | GB 4943.1 (for PMF-24V240WCGB) |
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| UKCA | In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 |
| Galvanic Isolation (Input to Output) | 3.0 KVac |
| Input to Ground | 2.0 KVac |
| Output to Ground | 0.5 KVac EMC |
| Emissions (CE & RE) | CISPR 32, EN/BS EN 55032, FCC Title 47: Class B |
| Immunity | EN/BS EN 55024 |
| Electrostatic Discharge (IEC 61000-4-2) | Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV |
| Radiated Field (IEC 61000-4-3) | Level 3 Criteria A1) 80 MHz – 1 GHz, 10 V/M with 1 kHz tone / 80% modulation |
| Electrical Fast Transient / Burst (IEC 61000-4-4) | Level 3 Criteria A1) 2 kV |
| Surge (IEC 61000-4-5) | Level 3 Criteria A1) Common Mode 2): 2 kV Differential Mode 3): 1 kV |
| Conducted (IEC 61000-4-6) | Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms |
| Power Frequency Magnetic Fields (IEC 61000-4-8) | Criteria A1) 10 A/Meter |
| Voltage Dips and Interruptions (IEC 61000-4-11) | 100% dip; 1 cycle (20 ms); Self Recoverable |
| Low Energy Pulse Test (Ring (IEC 61000-4-12) | Level 3 Criteria A1) |
| Wave) | Common Mode 2): 2 kV Differential Mode 3): 1 kV |
| Harmonic Current Emission | IEC/EN/BS EN 61000-3-2, Class A and Class D |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line) PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ Block Diagram Device Descriptions |
| Item | Device Description PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ Dimensions PMF-24V240WCG☐: Front Face L x W x H: 190 x 93 x 50 mm (7.48 x 3.66 x 1.97 inch) Note : Built-in cooling fan. Must prevent dust suction into power supply, or use natural convection power supply if any concerns. PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ PMF-24V240WCA☐: Terminal Block |
| Output Load De-rating VS Surrounding Air Temperature | Note |
| 1. | Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1. |
| 2. | If the output capacity is not reduced when the surrounding air temperature >70°C, the device will run into Over Temperature Protection. When activated, the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition. |
| 3. | In order for the device to function in the manner intended, it is also necessary to keep a safety distance of 20mm (0.78 inch) with adjacent units while the device is in operation. |
| 4. | Depending on the surrounding air temperature and output load delivered by the power |
| Fig. 1 | supply, the device can be very hot! > 50°C de-rate power by 2.5% / °C 5. If the device has to be mounted in any other orientation, please leave a message via the Contact Us form. Output Load De-rating VS Input Voltage voltage from 100 Vac to 264 Vac PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ Assembly & Installation power supply shall be mounted on minimum of 4 mounting holes using M4 screw of maximum 4 mm (0.16 inch) length (Refer to |
| Base Mounting (Horizontal) (Base Mounting (Vertical)) | Side Mounting (Horizontal) |
| Fig. 2 | Mounting Orientation should calculate and select the suitable wire specification (type/quantity/diameter) according to actual output current. The torque at the connector shall not exceed 13 Kgf.cm. The insulation stripping length should not exceed 0.275” or 7 mm. screw). Safety Distance D1 = 4.0mm Min. D2 = 20.0mm Min. – |
| Fig. 3 | Mounting Hole Locations and the Safety Distance addition, to ensure sufficient convection cooling, always maintain a distance of ≥ 20 mm from ventilated surfaces while the device is in operation. |
| Connector (Board Mounting) (Housing) | Terminal Remote ON/OFF Function |
| WST M2-I25002R (WST P2-I25002) | WST I25002PS-2 (Option) PMF Panel Mount Power Supply 24 V 240 W 1 Phase / PMF-24V240WC□□ is to keep a safe distance between the screw and internal components. holes at Ⓑ. This is to keep a safe distance between the screw and internal components. |
| Fig. 4 | Assembly Reference Improper Installations Saf ety Instructions components and equipments. In addition, to ensure sufficient convection cooling, always maintain a distance of ≥ 20 mm (0.79 inch) from ventilated surfaces while the device is in operation. not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning! It may cause: - Electric shock; Safety Hazard; Fire; Product failure. |
| Built-in Resistor R i (ohm) | Input Current (mA) |
| Output ON | Output OFF |